SS 16.4 Installation and Operation Manual
INSTALLATION
“Open Collector” Status Outputs, 16 Port Output Control
The SS 16.4 provides 16 open collector status outputs. The status outputs may be
configured to operate in one of three modes:
• The status output follows the associated channel. SW24-8 OFF.
• The status outputs a one-second pulse when the associated channel is
selected. SW24-8 OFF.
• Software control.
Refer to page 16 for special Relay/Open collector commands.
Relay Outputs, 8 Port Output Control:
The SS 16.4 contains 8 SPST (normally open) relays. Each relay may be latched
on, latched off or pulsed on by burst commands. The “pulse” time may be set from
100msec to 9.9 seconds. The default pulse length is one-second. Refer to page 16
for special Relay/Open collector commands. Each relay may be commanded to:
Latch On Turns on and stays on (through power failures) until turned off.
Latch Off Turns off and stays off (through power failures) until turned on.
Pulse Overrides latch; turns on for (default) second, then off.
“PIP” with Programmable Pulse Stretcher:
If DIP Switch SW24-8 is ON, the Programmable Pulse Stretcher (PIP) provides 24
“PIP” (GPI) inputs. Inputs must be 40ms or longer to qualify. The Programmable
Pulse Stretcher Duration may be globally set from 100ms to 2.55 seconds.
NOTE: When the unit ID is set to 0, no polling of “PIP” (GPI) inputs is
required.
NOTE:
Non-mechanical latch-
ing relays. When
power is removed, each
relay will open. When
power is restored, each
relay will return to the
pre-power failure state.
NOTE:
In burst mode, momen-
tary timing on each
relay can be set from
0.1 to 9.9 seconds.